Section 7
IEC 61850 communication engineering
96
All data sets, report control blocks and GOOSE control blocks
must be located at LD0/LLN0. Due to IED capability, there are
limitations regarding the maximum number of data sets, number
of entries in a data set and the number of report control blocks that
can be used.
3.
Add and/or reconfigure default data sets. The 650 series configured IED includes
a number of predefined data sets, but it is possible to add additional data sets and/
or reconfigure default data sets according to the requirements.
Note that reporting data sets shall only contain data intended to be
used by clients, for example for event handling.
4.
Configure report control blocks for each data set used for vertical
communication. The 650 series configured IED includes a number of predefined
report control blocks, but it is possible to add additional control blocks and/or
reconfigure default control blocks according to the requirements.
Up to 8 report clients can be configured.
5.
Connect the report control blocks to vertical IED clients. The report control
blocks are connected to the vertical clients in the SCD file for a 650 series pre-
configured IED. Check each IED client and configure them to the subnetwork
before connecting report control blocks to the clients.
6.
Create a GOOSE message data set for the sending IED. Define the content of the
data set according to the requirements.
The data set for GOOSE may contain signals on data attribute
level or on FCDA level. The latter is also called structured
GOOSE.
Ensure that the same GoID is set for sending and receiving
GOOSE messages.
Note that one data must only be included in one GOOSE data set.
Data set for GOOSE can not be empty.
7.
Create the GOOSE control block and connect it to the GOOSE message data set.
Be sure to check the parameters for the GOOSE control block and update as
required.
8.
Connect the GOOSE control block to the client IEDs, subscribing for GOOSE.
9.
Export the updated SCD file.
1MRK 511 284-UEN A
650 series
Engineering manual