Section 9
DNP3 communication engineering
9.4.1
112
IEC08000363 V1 EN
Figure 82:
CMT: Set Index menu
3.
Define the Starting index for this group and click OK.
Procedure to set class configuration:
1.
Click in the class field of the signal to change the class configuration.
2.
The Select Class window opens.
3.
Make the selection according to the definitions in the project and click OK to
close the window and get the new configuration, see
IEC08000338 V1 EN
Figure 83:
CMT: Select Class window

Configuring DNP3 class

In DNP3 the user classifies the signals and defines those signals that are not member
of any class. CMT has a default predefined organization of classes per signal type. In
the master station the classes can be polled in sequences according to the demands in
the project. Unsolicited reporting is possible as well.
Modify the organization of the classes for each signal individually.
Procedure
IEC08000338.vsd
1MRK 511 284-UEN A
IEC08000363.vsd
Figure
83.
650 series
Engineering manual