Section 5
Protection and control engineering
58
Validation on demand
To check the validity of an application configuration, click the 'Validate
Configuration' icon in the toolbar. ACT will check the application configuration for
formal correctness. Found problems are qualified in:
Warnings, marked by a yellow warning icon
Example: A variable connected to an output signal that is not connected.
Example: If the user connects output from higher execution order function
to inputs of lower execution order function.
Errors, marked by a red circle with a cross
Example: A mandatory input signal that is not connected.
Warnings will not prevent writing to the IED. Errors have to be corrected before
writing the application configuration to the IED. An application configuration can be
saved and ACT can be closed with open errors, but not written to the IED, see
39.
These problems are listed in the Output View under the Tab Application
Configuration. A double-click in the error or warning row will navigate to the
MainApplication>Page>Area where the problems are identified.
IEC09000614 V2 EN
Figure 39:
ACT: Validation on demand
Validation when writing to the IED
When writing the application configuration to the IED an automatic validation is
performed. The validation is the same as the manually demanded validation. Errors
will abort the writing.
1MRK 511 284-UEN A
Figure
IEC09000614_2_en.vsd