ABB 650 Series Engineering Manual page 33

Relion protection and control
Hide thumbs Also See for 650 Series:
Table of Contents

Advertisement

1MRK 511 284-UEN A
650 series
Engineering manual
Direct point-to-point link between PCM600 and the IED front port.
Indirect link via a station LAN or from remote via a network.
The physical connection and the IP address must be configured in both cases to enable
communication.
The communication procedures are the same in both cases.
1.
If needed, set the IP address for the IEDs.
2.
Set up the PC or workstation for a direct link (point-to-point), or
3.
Connect the PC or workstation to the LAN/WAN network.
4.
Configure the IED IP addresses in the PCM600 project for each IED to match the
IP addresses of the physical IEDs.
Setting up IP addresses
The IP address and the corresponding mask must be set via the LHMI for each
available Ethernet interface in the IED. Each Ethernet interface has a default factory
IP address when the IED is delivered. This is not given when an additional Ethernet
interface is installed or an interface is replaced.
The default IP address for the IED front port is 10.1.150.3 and the corresponding
subnetwork mask is 255.255.255.0, which can be set via the local HMI path Main
menu/Configuration/Communication/TCP-IP configuration/ETHFRNT:1.
Setting up the PC or workstation for point-to-point access to IEDs front
port
A special cable is needed to connect two physical Ethernet interfaces together without
a hub, router, bridge or switch in between. The Tx and Rx signal wires must be crossed
in the cable to connect Tx with Rx on the other side and vice versa. These cables are
known as cross over cables. The maximum length is 2 m. The connector type is
RJ-45.
IED
IEC09000096 V2 EN
Figure 8:
Point-to-point link between IED and PCM600 using a null-modem
cable
The following description is an example valid for standard PCs using Microsoft
Windows operating system. The example is taken from a Laptop with one Ethernet
interface.
RJ-45
Tx
Tx
Rx
Rx
Section 4
Setting up a project
PCM600
IEC09000096-2-en.vsd
27