3.1 Installation

3.1.1 Operating environment

Avoid mounting the unit in the following locations:
-Ambient temperatures outside the range of 0 ºC to 55 ºC.
-Ambient humidity outside the range of 30 % to 85 %RH (at 25 ºC, non-condensing).
-Sudden temperature changes causing condensation
-Corrosive and inflammable gases
-Excessive airborne dust, metal particle, or salts
-Benzine, thinner, alcohol or other organic solvents, or strong alkaline solutions such as ammonia or
caustic soda
-Excessive vibration or shock
-Direct sunlight
-Water, oil, or chemicals in any form including spray or mist
Measures regarding noise:
-The unit should be installed apart from the high voltage cables, high voltage equipment, power cables,
power equipment, or any other equipment that would generate high switching surges.
-The unit should also be installed apart from the devices which have radio transmitters.
-If noise occurs in the power supply line even after the above countermeasures are taken, you are
recommended to supply power through an insulation transformer, noise filter, or like.
Measures regarding heat discharge:
-Always amount the unit oriented with the LCD facing upward in order to prevent the generation of heat.
Do not amount the units vertically as shown below.
-Do not install the unit as shown below.
-Do not amount the unit above which generate large heat such as heaters, transformers, or large scale
resisters.
Note that the ambient temperature and electrical voltage are restricted when the mounting panel is
installed at the angle of 0 (horizontal) to 60.