Return Information Message From Sicam Ak To Cp-6010 - Siemens SICAM AK Manual

Rtus. redundancy,
Table of Contents

Advertisement

Redundancy via CP-6010
2.5.2.2.2

Return Information Message from SICAM AK to CP-6010

Select the values for the parameters
The Region and Component should be same as the control message.
Select the parameter
menu. This represents the status signal of SICAK AK to CP-6010.
Enter the same values for the parameters
parameterization of CP-6010.
Enter the values for the parameters IOA1,
Appendix A.2,
parameterization of CP-6010, for instance:
Select the following values via the pull-down menu:
Return_inform_function_(RED)
BSE_(RED)
PRE_(RED)
Afterwards click on Save.
Hinweis
For the parameterization of further return information signals, proceed as previously described.
For the configuration of SICAM AK B, proceed according to the same procedure as for SICAM AK A.
The following values must be updated in the SICAM AK B:
• Region
• Component
• CASDU
112
Lk_Reg
as
Redundancy return information
Lk_Cat
Configuration for SICAM AK to CP-6010
as
not used
as
not used
Unrestricted
and
via the relevant pull-down menu.
Lk_Comp
via the relevant pull-down
and
as provided in the web
CASDU1
CASDU2
and
for the module as provided in
IOA2
IOA3
(start address as provided in the web
= 65,
= 5,
IOA1
IOA2
IOA3
as
redundancy state
SICAM RTUs, SICAM AK Redundancy
Edition 10.2016, DC2-026-2.07
= 0).