1.3.2.3

Settings for BSEs (AU Redundancy)

In the OPM system technique you have selected Redundancy control under the node
Redundancy below the M-CPU and chosen the following entry in the Value dropdown list:
Line-by-line redundancy switchover with SCA-RS
Select Settings for BSEs (line. red. w. SCA-RS):
Settings for BSEs (line-by-line redundancy switchover with SCA-RS)
Column
name/Parameter
Priority assignment
Option: switchable
In the OPM system technique you have selected Redundancy control under the node
Redundancy below the M-CPU and chosen the following entry in the Value dropdown list:
Line-by-line redundancy switchover with application-related voting
Select Settings for BSEs (line. red. w. appl. voting):
SICAM RTUs, SICAM AK Redundancy
DC2-026-2.07, Edition 10.2016
Description/Value
Defines, for which SEs the priorities should be
valid after the occurrence of an error
The affected systemelement:
The affected BSE and its PRE:
All systemelements:
Defines, whether the voter should switchover the
defined BSE (System element is being switched to
passive) or not (Systemelement is not being
switched to passive)
Unrestricted
Redundancy via SCA-RS
Comment
The parameter is valid for
the selected BSE. The PE
(if available) is switched
passive indirectly: the filter
acts in the direction of the
PE, the data from the PE
are flagged with R-Bit.