Redundancy via SCA-RS
Establishing an electrical connection with a cable longer than 10 m
If it is necessary to lay a more than 10 m long electrical cable (up to max. 100 m)
a plenum cable has to be used.
Such a connection occurs in the following configurations in this document:
Point-to-point-traffic electrical (max. 15 m with V.28)
Multi-point traffic electrical (max. 15 m with V.28)
LAN communication electrical (max. 100 m with Ethernet)
cabinet 1
component 1
RJ45
TF5-200 (1,5m)
TF5-201 (3m)
TF5-202 (5m)
wall socket or
patch panel
Necessary modules and cables
Designation
Cable
Installation cable Cat.5 (4x2x0.5) AWG24
RJ-45/open end
Plenum cable
Installation cable Cat.5 (4x2x0.5) AWG24
Installation via wall socket or patch field
Patch panel
TP_Patch panel 24 Port 1HU, 6M
X-Port STP Box Cat.5e screened (4, 8, 12 Port)
Wall socket
TP_socket 2 x RJ-45 30° AP Cat.5
TP_connection module 1 x RJ-45 Cat.5
Assembly base for TS35
44
cabinet 2
TF5-200 (1,5m)
TF5-201 (3m)
TF5-202 (5m)
plenum cable, ca. 100 m
TF5-010
Unrestricted
component 2
RJ45
wall socket or
patch panel
Item Number / MLFB
TF5-200 (1.5m) / 6MF13140FC000AA1
TF5-201 (3m) / 6MF13140FC010AA1
TF5-202 (5m) / 6MF13140FC020AA1
TF5-010 / 6MF13140FA100AA1
T41-269 / 6MF13042BC600AA1
TEL+TS53.....
T41-286 / 6MF13040BC860AA1
T41-287 / 6MF13040BC870AA1
T41-291 / 6MF13041BC010AA1
SICAM RTUs, SICAM AK Redundancy
Edition 10.2016, DC2-026-2.07