Siemens SICAM AK Manual page 124

Rtus. redundancy,
Table of Contents

Advertisement

Configuration of SICAM AK and CP-6010
3.1
Overview
The board rack CM-2848 is primarily designed for communication and route redundancy.
Hint:
It is NOT possible to realise plants compliant with safety relevant requirements (SIL) since a single failure
within the power supply could lead to a switching-off the board rack completely.
A full AU-redundancy cannot be sufficiently achieved, although the propability that a single failure leads to
a power shutdown is very low.
3.1.1
System Components
The SICAM AK3 redundancy system cosists of:
1 board rack CM-2848 with 17 slots
2 modules CP-2016
1-2 power supply modules PS-263x possible
C-CPUs und PEs, refer to the following figure:
124
Unrestricted
SICAM RTUs, SICAM AK Redundancy
Edition 10.2016, DC2-026-2.07