Redundancy via CP-6010
2.2

CP-6010 (Redundancy Voter)

2.2.1

Power Supply and Firmware

Each module CP-6010 is supplied with voltage via a module PS-663x. The mounting takes
place on a DIN rail.
Once the respective CP-6010 is supplied with voltage, LEDs on the front panel indicate the
readiness for operation and errors, as well as the communication states of the Ethernet and of
the serial interface.
When the entire SICAM AK Redundancy system is started up and the communication is
established, the supervision of the both systems SICAM AK starts by means of the active
CP-6010:
Determination of the active SICAM AK
Monitoring of the errors from both systems SICAM AK
Switchover of the active SICAM AK based on the severity of the errors
In both CP-6010 a SD card with the current version of the firmware RED26 must be inserted.
The firmware contains the redundancy function and the user interface (web pages) for the
parameterization).