Redundancy via SCA-RS
Column name/
Parameter
Red_sync
monitoring timeout
In the OPM system technique select the node Singular Ax-PEs under C4:CP-
2017/PCCX25
(the node is visible if you have selected the value HSL with singular Ax-PEs for the
parameter Red_Sync Mode)
Column name/
Parameter
Automatic update
after going periphery
failure
Automatic bus-
switchover at bus
error
60
Description/Value
Defines how long the synchronization can
take: 0.1 -100 seconds. After this time period
in seconds has expired an error message is
generated.
Description/Value
Enabling for an automatic update of the
open/closed loop control function after every
going peripheral element failure on the passive
BSE (YES or NO)
Enabling of an automatic bus switchover with
bus error, (YES or NO)
Unrestricted
Comment
If the CAEx plus application
is very extensive, you require
a higher value.
The same applies for
redundant AUs, that
are far apart from each
other (redundancy
synchronization over a
separate fast data
connection)
Comment
The parameter is relevant for
the BSE with the singular PE:
if one PE restarts, after a
going failure of the PE on the
passive BSE the parameter
becomes effective
With a partial bus failure and
route redundancy (here: the
coupling of the singular PE
over various routes) a
redundancy switchover is
achieved without PE failure, if
the passive BSE reaches all
PEs, everything is OK there
and there are no higher
priority errors present.
SICAM RTUs, SICAM AK Redundancy
Edition 10.2016, DC2-026-2.07