Connector Pin Assignment; Configuration Switch - Siemens SICAM AK Manual

Rtus. redundancy,
Table of Contents

Advertisement

2.3.3

Connector Pin Assignment

The following table displays the pin assignment of the connector X3 for the cable between
both CP-6010. This connection is required for the backup serial communication using a
protocol according to the standard IEC 60870-5-101 over RS-422.
X3: 6-pin screw terminal
CP-6010-1
Pin 1
screen
Pin 2
TXD+
Pin 3
TXD-
Pin 4
RXD+
Pin 5
RXD-
Pin 6
GND
2.3.4

Configuration Switch

The following table describes the setting of the configuration switch S1 for the serial interface .
(RS-422).
Mode
4-wire with line termination
SICAM RTUs, SICAM AK Redundancy
DC2-026-2.07, Edition 10.2016
CP-6010-2
Pin 1
screen
Pin 4
RXD+
Pin 5
RXD-
Pin 2
TXD+
Pin 3
TXD-
Pin 6
GND
Switch 1
Switch 2
OFF
OFF
Unrestricted
Redundancy via CP-6010
Switch 3
Switch 4
ON
ON
95