Siemens SINAMICS S120 Manual page 127

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Table 4- 30
Technical data of the PM240-2, FSB (400 V)
Line voltage 3-phase 380 ... 480 V AC ± 10%
Article No.
without integrated line filter
with integrated line filter
Output current
Rated current I
1)
n
Base load current I
H
for S6 duty (40 %) l
S6
Peak current l
max
Type rating
2)
based on I
n
based on I
H
Rated pulse frequency
Max. pulse frequency
Power loss
Cooling air requirement
Sound pressure level LpA (1 m)
24 V DC supply
for the Control Unit
Rated input current
3)
Resistance value of the external
braking resistor
Max. cable length
to braking resistor
Line supply connection L1, L2, L3,
PE
Motor connection U2, V2, W2
DC-link connection, connection for
braking resistor
DCP/R1, DCN, R2
Max. motor cable length
4)
shielded/unshielded
Degree of protection
Weight
Without line filter
With line filter
AC Drive
Manual, (GH6), 07/2016, 6SL3097-4AL00-0BP5
6SL3210–
1PE21-1UL0
1PE21-1AL0
A
10.2
A
7.7
A
11.2
A
15.4
kW
4.0
kW
3.0
kHz
4
kHz
16
kW
0.11
l/s
9.2
dB
61.5
A
1.0
A
13.3
Ω
≥ 75
m
15
Screw-type terminals
Cross head M2.5
Conductor cross section: 1.5 ... 6 mm
Tightening torque: 0.6 Nm
m
50/100
IP20
kg
2.9
kg
3.1
4.2 Blocksize Power Modules (PM240-2)
Internal
6SL3210–
6SL3210–
1PE21-4UL0
1PE21-8UL0
1PE21-4AL0
1PE21-8AL0
13.2
18.0
10.2
13.2
14.5
19.8
20.4
27.0
5.5
7.5
4.0
5.5
4
4
16
16
0.15
0.2
9.2
9.2
61.5
61.5
1.0
1.0
17.2
22.2
≥ 75
≥ 75
15
15
2
2.9
3.0
3.1
3.2
Power Modules
Push-through
6SL3211–
1PE21-8UL0
1PE21-8AL0
18.0
13.2
19.8
27.0
7.5
5.5
4
16
0.2
5)
9.2
61.5
1.0
22.2
≥ 75
15
in the cabinet:
IP20
outside: IP54
3.6
3.9
127

Advertisement

Table of Contents
loading

Table of Contents