Advertisement

4.3.2.2

Terminal Block X9

Table 4- 39
Terminal block X9
Terminal
1
2
3
4
5
6
7
8
Note
If the "Safe Torque Off" function is selected, 24 V DC must be applied to terminal -X9:7 and
terminal -X9:8 must be grounded. Upon removal, pulse inhibit is activated.
4.3.2.3

DCPS, DCNS connection for a dv/dt filter

Table 4- 40
Frame size
FX
GX
The connecting cable is fed-out downwards through the Power Module.
4.3.2.4

X41 EP terminal / temperature sensor connection

Table 4- 41
Terminal block -X41
Terminal
1
2
3
4
Max. connectable cross-section: 1.5 mm²
AC Drive
Manual, (GH6), 07/2016, 6SL3097-4AL00-0BP5
Signal name
P24V
M
Reserved, do not use
Reserved, do not use
Main contactor
Main contactor
EP +24 V (Enable Pulses)
EP M1 (Enable Pulses)
DCPS, DCNS
Cross-section that can be connected
1 x 35 mm²
1 x 70 mm²
Function
EP M1
(Enable Pulses)
EP +24 V
(Enable Pulses)
-Temp
+Temp
Technical data
Voltage: 24 V DC (20.4 ... 28.8 V)
Current consumption: max 1.4 A
240 V AC/ max. 8 A
30 V DC/ max. 1 A
Supply voltage: 24 V DC (20.8 V ... 28.8 V)
Current consumption: 10 mA
The pulse inhibit function is only available when Safety
Integrated Basic Functions are enabled.
Terminal screw
M8
M8
Technical data
Supply voltage: 24 V DC (20.4 ... 28.8 V)
Current consumption: 10 mA
Temperature sensor KTY84-1C130 / PTC / PT100 /
PT1000 sensors
Power Modules
4.3 Power Modules Chassis
143