6.2.4.4

Connecting the dv/dt filter compact plus Voltage Peak Limiter

Figure 6-14
Connecting the dV/dt filter compact plus Voltage Peak Limiter
Cable cross-sections
Table 6- 14
dV/dt filter compact plus Voltage
Risk of fire due to ground fault/short-circuit
Inadequate installation of the cables to the Motor Module DC link can result in a ground
fault/short-circuit and place persons at risk as a result of the associated smoke and fire.
• Apply the local installation regulations to avoid this fault.
• Protect the cables against mechanical damage.
• Also implement one of the following measures:
Damage to the du/dt filter compact due to mechanical load on connections
The connections on the dv/dt filter compact have not been designed for the direct
mechanical connection of the motor cables.
• Take measures on the installation to ensure that the connections cannot be deformed
AC Drive
Manual, (GH6), 07/2016, 6SL3097-4AL00-0BP5
Cable cross-sections for connections between a dV/dt filter and Power Module
Peak Limiter
6SL3000-2DE32-6EA0
6SL3000-2DE35-0EA0
WARNING
– Use cables with double insulation.
– Maintain adequate clearance, e.g. by using spacers.
– Lay the cables in separate cable ducts or conduits.
WARNING
by the mechanical load exerted by the connected cables.
Cross-section
[mm²]
16
25
Motor-side power components
6.2 Chassis
Connection on dV/dt filter
M8 screw/12 Nm
M8 screw/12 Nm
213