6.1 Blocksize
6.1.1.4

Mounting

The motor reactors for Power Modules PM240-2, frame sizes FSA to FSF, are dimensioned
for installation in cabinets. The motor reactor is installed on the mounting surface next to the
Power Module.
Table 6- 1
Article number
6SL3202-0A16-1CA0
6SL3202-0AE18-8CA0
6SL3202-0AE21-8CA0
6SL3202-0AE23-8CA0
6SE6400-3TC03-8DD0
6SE6400-3TC07-5ED0
6SE6400-3TC14-5FD0
6SL3000-2BE32-1AA0
6SL3000-2BE32-6AA0
6SL3000-2AH31-0AA0
6SL3000-2AH31-5AA0
6.1.1.5

Electrical connection

Note
Approved cables for UL applications
Use only 75° C copper cables.
Table 6- 2
Securing the connection cables to the motor reactor
Article number
6SL3202-0AE16-1CA0
6SL3202-0AE18-8CA0
6SL3202-0AE21-8CA0
6SL3202-0AE23-8CA0
6SE6400-3TC03-8DD0
6SE6400-3TC07-5ED0
6SE6400-3TC14-5FD0
190
Mounting of motor reactors for PM240-2 Power Modules
Fastening
4 x M4 screws
4 x M4 nuts
4 x M4 washers
4 x M5 screws
4 x M5 nuts
4 x M5 washers
4 x M6 screws
4 x M6 nuts
4 x M6 washers
4 x M8 screws
4 x M8 nuts
4 x M8 washers
Connection to the Power Module/motor
connection
Fastening
4 mm
screw terminals
2
10 mm
screw terminals
2
16 mm
screw terminals
2
Flat connector for M6
cable lug
Flat connector for M8
cable lug
Tightening
Fastening
torque
0.6 ... 0.8 Nm
M4 studs
1.5 ... 1.8 Nm
M5 studs
2.0 ... 4.0 Nm
M5 studs
6 Nm
M6 screw
13 Nm
M8 screw
Manual, (GH6), 07/2016, 6SL3097-4AL00-0BP5
Tightening torque
3 Nm
5 Nm
10 Nm
25 Nm
PE connection
Tightening
torque
3 Nm
5 Nm
5 Nm
10 Nm
25 Nm