Motor-side power components
6.2 Chassis
Risk of burns due to high surface temperature of the du/dt filter compact
The surface temperature of the du/dt filters compact may exceed 80 °C. You can be
severely burnt when touching the surface.
• Mount the du/dt filters compact so that they cannot be touched. If this is not possible, at
NOTICE
Damage to the Voltage Peak Limiter due to interchanged connections
The Voltage Peak Limiter will be damaged if the input and output connections are
interchanged on devices with the article numbers 6SL3000-2DE41-4EA0, 6SL3000-2DG38-
1EA0, and 6SL3000-2DG41-3EA0.
• Connect the incoming cable from the DC link of the Motor Module to DCPS, DCNS.
• Connect the outgoing cable for the du/dt reactor to 1U2, 1V2, 1W2.
NOTICE
Damage to the dV/dt filter compact by using components that have not been released
When using components that have not been released, damage or malfunctions can occur
at the devices or the system itself.
• Only use a dV/dt filter compact that SIEMENS has released for SINAMICS.
NOTICE
Damage to the du/dt filter compact by exceeding the maximum output frequency
The maximum permissible output frequency when a dv/dt filter compact is used is 150 Hz.
The du/dt filter compact can be damaged if the output frequency is exceeded.
• Operate the du/dt filter compact with a maximum output frequency of 150 Hz.
NOTICE
Damage to the du/dt filter compact during continuous operation with low output frequencies
Uninterrupted duty at an output frequency less than 10 Hz can result in thermal overload
and destroy the du/dt filter.
• When using a du/dt filter compact plus voltage peak limiter do not operate the drive
• You may operate the drive for a maximum load duration of 5 minutes at an output
210
CAUTION
the dangerous locations, attach an appropriate warning note that is clearly visible and
easy to understand.
continuously with an output frequency less than 10 Hz.
frequency less than 10 Hz, provided that you then select operation with an output
frequency higher than 10 Hz for a period of 5 minutes.
Manual, (GH6), 07/2016, 6SL3097-4AL00-0BP5