Procedure
● Make sure that the device does not receive a power-on command (e.g. from the keyboard
or terminal block).
● Connect the forming circuit.
● While forming, the incandescent lamps must become less bright or go completely dark. If
the incandescent lamps continue to be brightly lit, a fault has occurred in the drive unit or
in the wiring.
● For forming using resistors, the module must remain in the circuit for approx. 1h. The
resistors will become very hot if there is a fault in the unit (surface temperature > 80 °C).
AC Drive
Manual, (GH6), 07/2016, 6SL3097-4AL00-0BP5
Service and maintenance
11.4 Forming the DC link capacitors
407