Configuring the instructions
4.6 Programming the Ident profile
Table 4- 50
Parameter
CMD
OFFSETBUFFER
ATTRIBUTES
EPCID_UID
LEN_ID
RXREF
72
TAG-STATUS
Value / description
0x73
Offset in the "RXREF" receive buffer
Identifier of the status modes / possible entries:
RF200: 0x83
RF300 (RF300T): 0x04, 0x82
RF300 (ISO): 0x83
RF300 Gen2: 0x83
RF600 (R620R, RF630R): 0x84, 0x85
Buffer for up to 62 bytes EPC-ID, 8 bytes UID or 4 bytes handle ID.
2 - 62-byte EPC-ID is entered at the start of the buffer (length is
set by "LEN_ID")
8-byte UID is entered at the start of the buffer ("LEN_ID = 8")
4-byte handle ID must be entered in the array element [5]-[8]
("LEN_ID = 8")
Default value: 0x00 ≙ unspecified single tag access
Length of the EPC-ID/UID
Received status data
You will find the data structure of the status modes in the section
"Tag_Status (Page 49)".
Ident profile, Add-on instruction for Rockwell systems