(19) RS-485 connection diagram 19)
GOT side
SDA1(TXD1+)
6
SDB1(TXD1-)
8
SG
2
SDA2(TXD2+)
5
SDB2(TXD2-)
7
RDA1(RXD1+)
10
RDB1(RXD1-)
12
RSA(RTS+)
14
RSB(RTS-)
16
CSA(CTS+)
18
CSB(CTS-)
20
NC
1
NC
3
NC
4
RDA2(RXD2+)
9
RDB2(RXD2-)
11
NC
13
NC
15
NC
17
NC
19
*1
Pin No. of temperature controller differs depending on the model. Refer to the following table.
Signal
SDB (+)
SDA (-)
RDB (+)
RDA (-)
*2
Terminating resistor should be provided for a GOT and a temperature controller which will be a terminal.
*3
Set the terminating resistor of GOT side which will be a terminal.
➠ ■3.
*4
Connect FG grounding to the appropriate part of a cable shield line.
Temperature
* 3
controller
* 1
RSB(+)
RSA(-)
SG
* 4
GREEN
GREEN
Series
Series
UT32A/UP32A/
name
UT/UP/
US
UM
Pin No.
Pin No.
23
21
24
22
25
23
26
24
SG
27
25
Connecting terminating resistors
* 4
Terminating resistor(220Ω 1/4W)
Model of temperature controller
UTAdvanced Series
UT35A/UP35A/
UT55A (product
condition A)/
UM33A
UP55A (product
condition A)
Pin No.
Pin No.
301
407
302
408
304
410
305
411
303
409
8.3 Connection Diagram
Temperature
controller
* 1
RSB(+)
RSA(-)
SG
* 2
UT55A (product
condition B)/
UT75A
UP55A (product
condition B)
Pin No.
Pin No.
501
1
502
2
504
4
505
5
503
3
8 - 29