Mitsubishi Electric GOT2000 Series Connection Manual page 496

Graphic operation terminal (non-mitsubishi electric products 2)
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

■4. Connected Ethernet Controller Setting
(1) Ethernet connection type: FETCH/WRITE
This section describes [Connected Ethernet Controller Setting] when [SIEMENS S7(Ethernet)] is selected for the
model.
Item
Host
Net No.
*1
Station
Unit Type
IP Address
FETCH Port No.
WRITE Port No.
Communication
*1
15 - 18
15.3 Ethernet Connection
The host is displayed. (The host is indicated with an asterisk (*).)
Set the network No. of the connected Ethernet module.
(Default: blank)
Set the station No. of the connected Ethernet module.
(Default: blank)
SIEMENS S7 (fixed)
Set the IP address of the connected Ethernet module.
(Default: blank)
Set the FETCH port No. of the connected Ethernet module.
(Default: 2000)
For the WRITE port No. of the connected Ethernet module, the value that
the FETCH port No. is incremented by one is set automatically.
(Default: 2001)
TCP (fixed)
Set different values for [GOT Station] of [Detail Setting] and [Station] of [Connected Ethernet Controller Setting].
■2. Communication detail settings
Description
Set value
1 to 239
1 to 64
SIEMENS S7
(fixed)
PLC side IP address
1024 to 65534
1025 to 65535
TCP (fixed)