Connecting to Ethernet Interface Module (F3LE01-5T, F3LE11-0T)

■1. Switch settings of Ethernet Interface Module
Set the switches accordingly.
(1) IP address switch
Set the IP address with eight Hex rotary switches on the side of the base unit
(2) Condition setting switch
Set the data format, write protection, line processing at TCP timeout error or operation mode with the DIP switch on
the side of the base unit.
Switch No.
1
2
3
4
5
6
7
8
*1
7 - 28
7.3 Ethernet Connection
POINT
POINT
POINT
Switch setting
Set the switches before mounting the Ethernet Interface Module on the base unit.
F3LE01-5T
Hexadecimal
Decimal
Description
Data
code
Write
protect
Reserved
Line processing
on TCP
*1
timeout
Operation mode
Applicable to only F3LE01-5T.
Condition setting
switch
IP address switch
Right side view without the cover
C0
A8
FA
192
168
250
1 2 3 4 5 6 7 8
OFF
OFF (ASCII)
OFF (not protect)
ON (not available),
OFF (always)
OFF (close the line)
OFF (normal operation)
F3LE11-0T
D2
210
Set value