This parameter makes it possible to select between three
different actions of the softstarter when the protection is
activated. It is active only if the phase reversal protection
is selected.
Stop–M
Stop–A
Ind
3DUDPHWHU
'HIDXOW YDOXH 6HWWLQJ UDQJH
WH[W
Ph Rev Op Stop–M
 37& SURWHFWLRQ
3DWK LQ PHQX
0HQX6(77,1*6)XQFWLRQDO 6HWWLQJV
3URWHFWLRQV37&
The softstarter has an input for an external PTC thermistor
that can be used independent of the built-in electronic
overload protection status.
3DUDPHWHU
'HIDXOW YDOXH 6HWWLQJ UDQJH
WH[W
PTC
No
The motor stops and a manual reset is
required before restart.
The motor stops and an automatic reset is
performed when the fault disappears.
The motor continues to run but a fault indi-
cation is given.
Stop–M, Stop–A,
Ind
Yes, No
&KDSWHU 
)XQFWLRQV
'HVFULSWLRQ
Type of operation
for phase rever-
sal protection
'HVFULSWLRQ
PTC protection