ABB PST Series Installation And Commissioning Manual page 141

Table of Contents

Advertisement

1SFC132003M0201
 )UHTXHQF\ IDXOW W\SH RI RSHUDWLRQ
3DWK LQ PHQX
0HQX6(77,1*6)XQFWLRQDO 6HWWLQJV
)DXOWV)UHT ) 2S
This parameter makes it possible to select between two
different actions of the softstarter if the frequency is out of
range (frequency fault).
Stop–M
Stop–A
3DUDPHWHU
'HIDXOW YDOXH 6HWWLQJ UDQJH
WH[W
Freq F Op Stop–M
 +HDW VLQN RYHUWHPSHUDWXUH IDXOW
W\SH RI RSHUDWLRQ
3DWK LQ PHQX
0HQX6(77,1*6)XQFWLRQDO 6HWWLQJV
)DXOWV+6 7HPS 2S
This parameter makes it possible to select between two
different actions if the heat sink temperature of the
softstarter is too high.
Stop–M
Stop–A
3DUDPHWHU
'HIDXOW YDOXH 6HWWLQJ UDQJH
WH[W
HS Temp
Stop–M
Op
The motor stops and a manual reset is
required before restart.
The motor stops and an automatic reset is
performed when the fault disappears.
Stop–M, Stop–A
The motor stops and a manual reset is
required before restart.
The motor stops and an automatic reset is
performed when the fault disappears.
Stop–M, Stop–A
&KDSWHU 
)XQFWLRQV
'HVFULSWLRQ
Type of operation
for frequency fault
'HVFULSWLRQ
Type of opera-
tion for heat sink
over temperature
fault
141