ABB PST Series Installation And Commissioning Manual page 164

Table of Contents

Advertisement

&KDSWHU 
7URXEOH VKRRWLQJ
6WDWXV
0RWRU RYHUORDG SURWHFWLRQ
Power on
Fault
Protection
2TQV /QVQT 1.
4GUGV
164
 3URWHFWLRQ LQGLFDWLRQ
3RVVLEOH FDXVH
The motor has been exposed to
an overload condition because
the current over a certain time is
too high.
(The load on the motor shaft is
too high)
$CEM
6ROXWLRQ
,Q /LQH
$W VWDUW
• Check and correct the reason for the
overload. Check that current limit level is
not set too low.
• Check that the ramp time for start is not
too long.
• Check that correct overload class is
used.
• Check that parameter Setting Ie is cor-
rect.
&RQWLQXRXV UXQ
• Check and correct the reason for the
overload.
,QVLGH 'HOWD
$W VWDUW
• Check and correct the reason for the
overload.
• Check that current limit level is not set
too low.
• Check that the ramp time for start is not
too long.
• Check that correct overload class is
used.
• Check that parameter Setting Ie is set to
e
58% (
) of the rated motor current.
1
3
&RQWLQXRXV UXQ
• Check and correct the reason for the
overload
1SFC132003M0201