Mitsubishi Electric AE-200A Instruction Book page 80

Air conditioning control system
Hide thumbs Also See for AE-200A:
Table of Contents

Advertisement

[6] Registering general equipment to a group
(1) To register general equipment to a group, touch the "Unit
selection" button under the target group name. A screen to
select the units will appear.
Select [General Equipment (via PAC-YG66DCA)] in the
[Model] section, and select the unit address of the DIDO
controller (PAC-YG66DCA) that is connected to the
general equipment to be registered.
The selected number will appear with an yellow-green
frame.
Then, select contact points to which the general equipment
are connected, and touch the address assigned to another
unit to register the first selected item to the group. The
yellow-green frame will change to an orange frame. (The
item with a yellow-green frame is the currently selected
unit, and the ones with an orange frame are the units that
are already registered to a group.)
Touch again to deselect.
Note: Each contact of DIDO controller counts as one unit.
Note: Each group can contain up to 16 general equipment.
Note: Up to six general equipment can be registered for each
DIDO controller.
Note: Air conditioners, Air To Water (PWFY) units, LOSSNAY
units, and HWHP (CAHV) units cannot be combined with
general equipment in one group. To change the registered
units to general equipment in the group to which air
conditioners, Air To Water (PWFY) units, LOSSNAY units,
or HWHP (CAHV) units are registered, unregister the air
conditioners, Air To Water (PWFY) units, LOSSNAY units,
or HWHP (CAHV) units first.
Note: General equipment groups cannot include remote
controllers or system controllers.
(2) To change the unit icon to be used, touch the icon under
the [Icon] section. A screen to select an icon will appear.
Select an icon to be used, and then touch [OK].
(3) In the [Allow Operations] section, make the setting to allow or disallow operation.
Select [In batch and on individual group] to allow the operator to turn on or off the general equipment
collectively or by the groups.
Select [On individual group] to allow the operator to turn on or off the general equipment by the groups.
Select [No operations (Monitor only)] to disallow the operator to turn on or off the general equipment.
(4) In the [Monitor] section, select which status will be used to reflect the units' ON/OFF status to the unit icons on
the [Monitor/Operation] menu screen.
Select [Output status] to use the status that is sent to the general equipment, and [Input status] to use the
status that is sent from the general equipment.
WT07190X01
80