[2] Registering PI controllers and metering devices
Follow the instructions below to make the system settings of the metering devices. Up to four metering devices can
be connected to a PI controller (PAC-YG60MCA).
Note: Although up to 15 PI controllers (PAC-YG60MCA) can be set for each AE-200/AE-50, the number of PI controllers in a
system with connection to one or more AE-50 controllers must be 20 or less.
PI controller icon
Metering device name
(1) Using the scroll bar, select the address to which the PI controller (PAC-YG60MCA) will be connected.
(2) Select the PI controller icon (
Note: Touch again to deselect.
(3) Touch the "Metering device name" button to display the keyboard. Enter the name of the metering device in 20
characters or less.
Note: The following characters cannot be used: <, >, &, ", or '
(4) Touch the "Pulse value" button to display the keypad. Enter
the pulse value of the metering device, and touch [OK].
Note: The settable range is between 0.01 and +100.
Note: If the pulse value field is left blank, the reading of the
metering device cannot be properly obtained. Be sure to set
the pulse value.
(5) Touch the "Measurement unit" button to select the measurement unit.
Note: The measurement unit can be selected from [kWh], [m3], [MJ], [--(no unit)], or [(blank)]. Select the blank when not using
a metering device.
Important
● Set the pulse value according to the metering device to be used. To ensure proper settings, first check the value
measured by the metering device and the value counted by the PI controller. Then, after a certain time, check
that both values have increased by equal values. (The values that the PI controller counts can be checked on the
[Measurement] display under the [Monitor/Operation] menu.)
(6) Touch [Save Settings].