Mitsubishi Electric AE-200A Instruction Book page 90

Air conditioning control system
Hide thumbs Also See for AE-200A:
Table of Contents

Advertisement

(2) System with an AE-200 controller connected to AE-50 controllers
Leave the default setting [Master] as it is.
Master
(3) System with a high-level system (i.e., TG-2000A) connected to AE-200 controllers
Leave the default setting [Master] as it is.
TG-2000A
[2] Old model compatibility mode
In the [Old model compatibility mode] section, select [ON] or [OFF].
When [ON] is selected, the Dual set point function and Prohibit Remote Controller function (Timer, Air Direction, Fan
Speed) cannot be used.
Note: If the setting is changed, the controller will reboot.
[3] Hold type
The Hold function is a function to disable the operations that were scheduled for air conditioning unit groups.
If the setting for [Hold] is set to [ON] on the operation settings screen under the [Monitor/Operation] menu and the
[Hold type] on the screen above is set to [Forced], the [Hold] setting can be cancelled only from the AE-200/AE-50.
If the [Hold type] is set to [Normal], the [Hold] setting can be cancelled from AE-200/AE-50, other system controllers,
or remote controllers.
Note: The Hold function can be used on the AE-200A/AE-50A, but not on the AE-200E/AE-50E.
Note: The Hold function cannot be used on general equipments.
Note: The setting [Forced] will not be effective on Air To Water (PWFY) unit groups, LOSSNAY unit groups, HWHP (CAHV) unit
groups, general equipment groups, and air conditioning unit groups that do not support the Hold function (i.e., Mr. Slim
M-Series/P-Series indoor units). If the setting for [Hold] is set to [ON] on those unit groups on the operation settings screen
and the [Hold type] on the screen above is set to [Forced], the setting [Normal] will be effective.
[4] Schedule: Season setting
In the [Schedule: Season setting] section, select [Available] to enable the seasonal settings of the weekly schedules
and [Not Available] to disable. Unless otherwise specified, leave the default setting [Available] as it is.
Note: The settings made on this screen on the AE-200 will be reflected on this screen on the AE-50.
WT07190X01
Master
AE-200
AE-50
Master
AE-50
Master
AE-200
Master
AE-200
Outdoor unit
Indoor unit
Outdoor unit
Indoor unit
Outdoor unit
Indoor unit
Outdoor unit
Indoor unit
90