When the External Temperature Interlock function is active, the set temperature will be adjusted as shown
below.
■ "Cool" and "Dry" modes
Outdoor temperature conditions
Outdoor temperature ≥
Set temperature + 1.5°C (3°F)
Outdoor temperature ≥
Set temperature + 4.5°C (9°F)
Outdoor temperature ≥
Set temperature + 6.5°C (12°F)
Outdoor temperature ≥
Set temperature + 7.5°C (14°F)
■ "Heat" mode
Outdoor temperature conditions
Outdoor temperature ≤
Set temperature - 4.0°C (8°F)
Outdoor temperature ≤
Set temperature - 6.0°C (11°F)
Outdoor temperature ≤
Set temperature - 8.0°C (15°F)
Outdoor temperature ≤
Set temperature - 10.0°C (18°F)
WT07190X01
36
Outdoor temperature
35
34
33
32
31
30
29
28
27
26
25
24
23
Set temperature
19
18
17
16
15
14
13
Set temperature after being adjusted
when [Control levels] is set to [±4°C]
12
(±8°F)
11
10
9
8
7
6
Set temperature after being adjusted
when [Control levels] is set to [±4°C]
(±8°F)
Set temperature
Time
Set temperature after being adjusted
Set temperature + 1°C (2°F)
Set temperature + 2°C (4°F)
Set temperature + 3°C (6°F)
Set temperature + 4°C (8°F)
Outdoor temperature
Time
Set temperature after being adjusted
Set temperature - 1°C (2°F)
Set temperature - 2°C (4°F)
Set temperature - 3°C (6°F)
Set temperature - 4°C (8°F)
96