Siemens LMV5 Series Technical Instructions page 205

Linkageless burner management system
Hide thumbs Also See for LMV5 Series:
Table of Contents

Advertisement

LMV Series 
 
 
Additional Tips for O
 Trim Commissioning and Tuning 
2
 
If the AZL52 displays that the O
under the following menu path: 
 
Operation > O2Ctrl activate 
 
Repeated deactivations can be caused by many different problems, including inaccurate load 
numbers. 
 
All of the points on the O
be less than an hour.  This is preferable, since ambient conditions (air temperature and barometric 
pressure) typically do not change a significant amount in one hour.
 
Every point on the O
 Ratio Control Curve must have a corresponding point on the rich limit (O
2
alarm) curve.  For Point 2 and above, every point on the O
corresponding point on the O
 
will occur.
 
If a point on the O
 Ratio Control Curve is changed (actuator positions), the corresponding point on 
2
the O
 Control Curve will be deleted.  The O
2
activated if points are missing on any of the curves (O
 
Considering the items above, if one point is changed on the O
Ratio Control Curve and the O
point is known to be based on the same ambient conditions.  Setting the O
the O
 Control Curve in a piecemeal fashion typically does not yield reliable O
2
 
The LMV52.240 can only decrease the air influencing actuator positions below their settings on the 
O
 Ratio Control Curve.  This is typically not an issue if the gap between the O
2
and the O
 Control Curve is large enough (1%).  The LMV52.440 can increase or decrease the air 
2
influencing actuator positions, so the gap between the O
Curve can be smaller (0.5%).  This also gives the LMV52.440 the ability to deal with more challenging 
applications such as FGR and low NOx mesh burners.
 
Most burners will flame fail in a safe way if operated too lean.  However, overly lean operation may 
be hazardous for some burner designs.  If one of these burners is encountered, the O
Curve can be set to function as the lean limit using the following menu path: 
 
Params & Display > O2Contr/Alarm > Gas/Oil Settings > O2 Alarm > Type O2 MaxValue 
 
Set this to "O2MaxCurve".  For this type of burner it is also recommended to set the operating mode 
of the O
 trim to "O2 Control", so a lockout will occur if the lean limit is reached. 
2
 
Params & Display > O2Contr/Alarm > Gas/Oil Settings > OptgMode = O2 Control 
 
SCC Inc. 
 
 
 trim has been automatically deactivated, it can be re‐activated 
2
 Control Curve should be completed in one session, and the session should 
2
 Control Curve. If this is not done, an immediate O
2
 trim will automatically deactivate and cannot be re‐
2
 Control Curve should be redone so that the Lambda Factor at each 
2
Page 33 
HOME
Document No. LV5‐1000 
 
 Ratio Control Curve must also have a 
2
 Ratio Control, O
 Control, O
2
2
 Ratio Control Curve, then the O
2
 Ratio Control Curve and 
2
 trim operation.
2
 Ratio Control Curve 
2
 Ratio Control Curve and the O
2
 
Technical Instructions 
 
2
 trim deactivation 
2
 
 Alarm).
2
 
2
 
 Control 
2
 Ratio Control 
2