LMV Series 
 
3‐1:  Parameters Introduction
 
The  Siemens  LMV5  has  a  number  of  parameters  that  can  be  adjusted  to  suit  the  wide  variety  of 
applications that exist in the burner / boiler and industrial heating market.  
 
These parameters are broken up into three main groups by password access: 
 
User 
Level access does not require a password, and encompasses all of the parameters that  an 
end user might have to view or adjust during the life of the burner / boiler.  
 
Service 
Level  access  does  require  a  password,  and  encompasses  all  of  the  user  level  parameters, 
plus  additional  parameters  that  a  service  technician  might  need  to  access  to  tune  or 
maintain the burner / boiler.  
 
OEM 
Level access  requires a different password than the service level, and enables the OEM  to 
access all available parameters, including safety‐related parameters.   
 
The parameters are accessed through the AZL5 in an outline‐type structure.  This structure is thoroughly 
illustrated  with  the  LMV5  Parameter  List  in  Section  3‐2.    An  explanation  of  how  to  use  the  LMV5 
Parameter List is shown below. 
 
Menu Path 
States the menu 
path necessary to 
SafetyTme1Gas (O) 
 
access the 
 
parameter.  Bold 
 
indicates the 
 
highest menu 
 
level. 
 
 
 
Params & Display> 
BurnerControl> 
Times> 
TimesStartup2 
*LMV51.0  is  not  shown  in  the  Parameter  List.    It  has  the  same  parameters  as  the  LMV51.1  with  the 
exception that the LMV51.0 has no "load controller" parameters. 
 
 
Section 3‐3 shows the sequence diagrams for each fuel train available in the LMV5 with the exception of 
HeavyOilHO (heavy oil with direct spark).  For an example of what each of these fuel trains looks like, see 
Section 4. 
 
 
SCC Inc. 
 
Parameter 
Default  Range 
5s 
SafetyTme1Oil (O) 
5s 
Interval1Gas (S) 
2s 
Interval1Oil (S) 
2s 
Figure 3‐1.1:  LMV5 Parameter List Legend 
Page 1 
HOME
 
 
Description 
When a fuel train with a 
pilot is used, this setting 
1‐10s 
defines... 
States if the parameter is 
available on an LMV51.1, 
1‐15s 
LMV52.2, or LMV52.4* 
When a fuel train is 
selected that has a pilot, 
this setting defines... 
0.2‐63s 
States what password 
level is required to 
access the parameter. 
Technical Instructions 
Document No. LV5‐1000 
x x x
Section 3 