Line Reactors - Siemens LMV5 Series Technical Instructions

Linkageless burner management system
Hide thumbs Also See for LMV5 Series:
Table of Contents

Advertisement

LMV Series 
 
 
As mentioned above, VFDs switch multiple IGBTs on and off very rapidly to generate a "modified" sine 
wave on all three phases going to the motor.  Doing this has some tradeoffs, one of which is electrical 
noise, or harmonics.  This noise is typically "wire borne" instead of airborne, and can cause issues with 
electronics in some situations.  Thankfully, electrical noise associated with VFDs can be mitigated using 
proper wiring techniques (connecting shields and grounds correctly) and by the proper application of 
line reactors and / or load reactors for some applications.  For difficult applications, EMC filters for the 
VFD are also available. 
 
Line Reactors 
 
Line reactors, or "chokes", are typically used when the impedance on the input side of the drive is low. 
Impedance on the input side of the drive is typically low when a relatively small VFD is being fed by a 
relatively large transformer.  In this situation, the supply side of the drive is "stiff", meaning that an 
instantaneous current draw by the drive will be met very quickly by the large transformer (think square 
wave form), causing voltage and current distortions in the power distribution system feeding the drive. 
In this situation, adding a line reactor will add reactance which opposes instantaneous current draw and 
"softens" the input side of the drive. 
  
Conversely, if the transformer feeding the drive is not large relative to the drive, the impedance on the 
input side of the drive is higher and the system is "softer".  In this situation, an instantaneous current 
draw by the drive will not be met as quickly, and the resulting voltage and current distortions in the 
power distribution system feeding the drive will be smaller.  An additional line reactor in this situation is 
not needed. 
 
 
Figure 5‐1:  Line Reactor Recommendation ‐ VFD (HP) vs Transformer (kVA) 