LEGEND - Password Access: (U)=User, (S)=Service, (O)=OEM, Shaded = Commonly Used, ** = Must Set, X = Has Function, / = Partial Function
Menu Path
Parameter
StartReleaseGas (O)
StartReleaseOil (O)
Params & Display>
AirPressureTest (O)
BurnerControl>
Configuration>
ConfigIn/Output
Config_PS-VP/CPI (O)
FGR-PS/FCC (O)
SCC Inc.
Default
Range
Sets the function of INPUT X7-03.2.
deactivated
1) deactivated - terminal has no function.
StartRelGas
StartRel
2) StartRelGas - input must be energized in phase 21-62.
CPI Gas
Gas
3) CPI Gas - proof of closure (POC) for gas valves.
CPI Gas+Oil
4) CPI Gas+Oil - proof of closure (POC) for gas and oil valves wired on the same terminal.
CPI Oil
5) CPI Oil - proof of closure (POC) for oil valves.
Sets the function of INPUT X6-01.1.
1) activated - input must be energized in phase 21-62, typically used for an atomizing media
activated
pressure switch.
activated
deactivated
2) deactivated - terminal has no function.
HT/FG-RedCo
3) HT/FG-RedCo - input for a redundant contact when using an external flame safeguard. This
input is inverse of the main contact on terminal X6-01.3. See parameter HeavyOilDirStart for
more information on external flame safeguards (LMV52 only).
Activates or deactivates INPUT X3-02.1, the combustion air pressure switch. Activate for
activated
forced or induced draft burners. Can also be set to "deactInStby", so that the status of the air
activated
deactivated
pressure switch is not evaluated in standby. However, the burner will not start until INPUT
deactInStby
X3-02.1 is de-energized.
Sets the function of INPUT X9-03.2.
1) PS-VP - pressure switch for use with automatic valve proving.
PS-VP
2) CPI Gas - proof of closure (POC) for gas valves.
CPI Gas
CPI Gas
3) CPI Gas+Oil - POC for gas and oil valves on the same terminal.
CPI Gas+Oil
4) CPI Oil - POC for oil valves.
CPI Oil
Note: Input can be deactivated by setting to PS-VP and de-activating valve proving at:
Params & Display > BurnerControl > ValveProving > ValveProvingType
Sets the function of INPUT X4-01.3.
1) FCC - checks the status of the fan motor starter.
FCC
2) FGR-PS - checks the status of an FGR pressure switch.
FGR-PS
3) deactivated - terminal has no function.
FCC
deactivated
4) PSdeactStby - checks the status of an FGR pressure switch but the pressure switch is not
PSdeactStby
evaluated in standby.
PS VSD
5) PS VSD - checks the status of a second air pressure switch based on VSD speed. See
RotSpeed PS on and RotSpeed PS off (not available on LMV51.1).
Page 12
HOME
Description
P - LIST
Technical Instructions
LV5-1000
LMV
x x x
/ x x
x x x
x x x
/ x x
Section 3