Load_Sw_From_Pc - Siemens LMV5 Series Technical Instructions

Linkageless burner management system
Hide thumbs Also See for LMV5 Series:
Table of Contents

Advertisement

LMV Series
LEGEND - Password Access: (U)=User, (S)=Service, (O)=OEM, Shaded = Commonly Used, ** = Must Set, X = Has Function, / = Partial Function
Menu Path
Parameter
LMV5x -> AZL (S)
Updating>
ParamBackup
AZL -> LMV5x (S)
Load_SW_from_PC (S)
Updating
Access w-out PW (U)
Access Serv (U)
PW Login
Access OEM (U)
Access SBT (U)
PW Logout
PW Logout (S)
LossFlameTest (U)
SLT Test (U)
SafetyCheckFunct
SLT-Testload Mod (U)
SLT-Testload Stg (U)
SCC Inc.
Default
Range
Go into parameter then
Transfers a parameter set from the LMV5x to the AZL5. Note that the working parameter set
press Enter to start
is in the LMV5, not the AZL5. Burner ID in LMV5 will overwrite burner ID in the AZL5.
Transfers a parameter set from the AZL5 to the LMV5. The burner ID of the LMV5 must be
blank (new LMV5) or must match the burner ID of the parameter set in the AZL5. This
feature is useful for transferring parameter sets to identical burners. NOTE: When
Go into parameter then
transferring parameter sets from the AZL5 to the LMV5, do not stop the transfer until
press Enter to start
"Backup Restore Finished Parameter BC : complete or BC : partial" is shown on the AZL
screen. This could take up to 5 minutes. Do not disturb the LMV5 while the backup restore is
in progress.
Go into parameter then
Enables updating of the AZL5 operating software via the ACS450 software. A .bin file
press Enter to start
supplies the new software for the AZL5.
Press Enter for access
Access without password. Also called user level.
3 to 8
9876
Access with service level password.
characters
4 to 8
START
Access with OEM level password.
characters
-
-
Access level not used.
Press Enter to log out
Deactivates all passwords, thus reducing access to user level.
Go into parameter then
Enables testing of the flame sensor input on the LMV5 by electronically interrupting the
press Enter to start
flame signal.
This enables the safety limit thermostat (SLT) test to check upper safety limits.
activated
activated - The internal load controller's setpoint AND switch-off threshold will be ignored,
deact
deactivated
allowing a test of a separate high limit control or pressure relief valve.
deactivated - feature is disabled.
100%
0-100%
This sets the load for the SLT test in modulating operation.
S3
S1-S3
This sets the load for the SLT test in staged operation.
Page 46
HOME
Description
P - LIST
Technical Instructions
LV5-1000
LMV
x x x
x x x
x x x
x x x
x x x
x x x
x x x
x x x
x x x
x x x
x x x
x x x
Section 3