Maxloadgas(Oil) - Siemens LMV5 Series Technical Instructions

Linkageless burner management system
Hide thumbs Also See for LMV5 Series:
Table of Contents

Advertisement

LMV Series
LEGEND - Password Access: (U)=User, (S)=Service, (O)=OEM, Shaded = Commonly Used, ** = Must Set, X = Has Function, / = Partial Function
Menu Path
Parameter
Params & Display>
RatioControl>
ProgramStop (S)
Gas/Oil Settings>
SpecialPositions
IgnitionPosGas or
IgnitionPosOil (S)
Params & Display>
IgnitionPosAir (S)
RatioControl>
IgnitionPosAux1 (S)
Gas/Oil Settings>
SpecialPositions>
IgnitionPosAux2 (S)
ResetlgnitPos
IgnitionPosAux3 (S)
IgnitionPosVSD (S)
Params & Display>
RatioControl>
CurveParams (S)**
GasSettings>
Params & Display>
Curve Settings (S)
RatioControl>
OilSettings>
CurveParams
Operation Mode (O)
Params & Display>
MinLoadGas(Oil) (S)
RatioControl>
Gas/Oil Settings>
LoadLimits
MaxLoadGas(Oil) (S)
SCC Inc.
Default
Range
For gas or oil firing, this parameter will stop the sequence in the selected phase. Useful for
commissioning and service work.
See
deact
The LMV5 can be held in the following phases: 24 Prepurge, 32 Prepurge FGR, 36 Ignition
Description
Position, 44 Interval 1 (pilot stabilize), 52 Interval 2 (main flame stabilize), 72 Postpurge
Position, 76 Postpurge FGR. Program Stop can also be deactivated.
Resets the ignition position of the fuel actuator(s) to an invalid value.
Resets the ignition position of the air actuator to an invalid value.
Go into parameter then
Resets the ignition position of the aux1 actuator to an invalid value.
press Enter to reset
Resets the ignition position of the aux2 actuator to an invalid value.
Resets the ignition position of the aux3 actuator to an invalid value.
Resets the ignition speed of the VSD to an invalid value.
This is where actuator position curves and VSD speed curves are set from low to high fire.
These position curves determine the fuel-air ratio for the burner across the firing range.
Fifteen points can be set from low to high fire. Typically ten points are set. Colons(:) indicate
Not Set
that the actuator is at the indicated position, (>) indicates the actuator is seeking the
indicated position, (#) indicates the aux 3 FGR actuator is being held at position due to an
FGR hold. If an O2 sensor is attached and activated (LMV52), the wet O2 value will also be
displayed on the screen.
Points 1-15
When a specific point is selected (point 2 for example), the LMV5 will prompt if the point is
to be 'changed' or 'deleted'. If 'change' is selected, then the LMV5 will prompt the user to
select 'followed' or 'not followed'. If 'followed' is selected, the LMV5 will drive the actuators /
VSD to the point, and then the point can be changed. If 'not followed' is selected, the LMV5
Not Set
will not drive to the point, but the point can still be changed.
NOTE : When 'not followed' is selected, the effect of actuator changes cannot be seen on a
combustion analyzer. If 'not followed' is selected, extreme caution must be used.
Modulating
Mod-
Operation mode for firing oil.
Two-stage
ulating
Three-stage
Sets the low fire load. During normal operation, the burner will not modulate below this
0-MaxLoad
0%
point. Set to reflect low fire fuel input. For a 10:1 turndown burner, set at 10%. Maximum
Gas(Oil)
setting limited by MaxLoadGas(Oil) .
MinLoadGas
Sets the high fire load. During normal operation, the burner will not modulate above this
100%
(Oil) -100%
point. Minimum setting limited by MinLoadGas(Oil) .
Page 19
HOME
Description
P - LIST
Technical Instructions
LV5-1000
LMV
x x x
x x x
x x x
x x x
x x
x x
x x
x x x
x x x
x x x
x x x
x x x
Section 3