Siemens LMV5 Series Technical Instructions page 273

Linkageless burner management system
Hide thumbs Also See for LMV5 Series:
Table of Contents

Advertisement

LMV Series
Example
Marking for data query or end of reply with data format 10 / 9 bits
Waiting time = 3.5 characters * 1000 * x bits / Baud rate
Baud rate [Baud]
Data query process
Time diagram
A data query is made according to the following time diagram:
where:
t0
t1
t2
Communication during the slave's internal handling time
During the slave's internal handling time, the master is not allowed to make any data queries. The slave
ignores data queries made during this period of time.
Communication during the slave's reply time
During the slave's reply time, the master is not allowed to make any data queries. Data queries made
during this period of time cause all data on the bus at this instant to be deleted.
SCC Inc.
9600
Marking for end = 3.5 characters (time is dependent on the Baud rate)
This time is dependent on internal handling; the maximum handling time is
dependent on the data type (internal and external data) and on the number
of data; for more detailed information, see below!
t2 ≥ 20 ms
This time is required by the device to switch from transmitting back to
receiving; this time must be observed by the master before a new data
query is made; it must always be observed, even if a new data query to
some other device is made
Page 3
HOME
Data format [bit]
10
9
Technical Instructions
Document No. LV5-1000
Waiting time [ms]
3.125
2.813
Section 8