Startadaption - Siemens LMV5 Series Technical Instructions

Linkageless burner management system
Hide thumbs Also See for LMV5 Series:
Table of Contents

Advertisement

LMV Series
LEGEND - Password Access: (U)=User, (S)=Service, (O)=OEM, Shaded = Commonly Used, ** = Must Set, X = Has Function, / = Partial Function
Menu Path
Parameter
CurrMode 0/4mA (S)
Scale20mA perc (S)
Scale20mA temp (S)
Params & Display>
Scale20mA press (S)
LoadController>
Configuration>
Scale20mA angle (S)
Analog Output
Scale 0/4mA (S)
StartAdaption (U)
Params & Display>
LoadController>
Adaption
AdaptionLoad (U)
Params & Display>
SW Version (U)
LoadController
SCC Inc.
Default
Range
0..20mA
Selects the output signal of X63 to be either a 0-20mA signal or a 4-20mA signal. NOTE: This
0..20mA
4..20mA
has no effect when OutValueSelection is set to "Load".
Scales the analog output for the percent values (other than Load). Specifically, this
100%
0-999.9%
parameter defines what percentage of Load 0, O2, Speed VSD, or Flame will output 20mA.
Scales the analog output for the temperature values. Specifically, this parameter defines
1562 F
32-3632 F
what temperature (read by Temp Pt1000,Temp Ni1000, etc.) will output 20mA.
Scales the analog output for the pressure value. Specifically, this parameter defines what
2 PSI
0-1449 PSI
pressure (read by Press X61) will output 20mA.
Scales the analog output for the actuators. Specifically, this parameter defines what angular
90 deg
0-90 deg
degrees will output 20mA.
Sets the start of the scale for every process value other than "Load". (The start of the scale
"Load 0" can be set here, but if "Load" is selected this parameter has no effect.) For example
: If parameter OutValueSelection is set to "Pos Air", CurrMode 0/4mA is set to 4mA,
0%
0-999.9%
Scale20mA angle is set to 90 deg, and Scale 0/4mA is set to 0%, then 12 mA will be output
when the air actuator is at 45 degrees, and 20mA will be output at 90 degrees. If all other
values are unchanged and Scale 0/4mA is now set to 50%, then 4 mA will be output when
the air actuator is 45 degrees, and 20mA will be output when the actuator is at 90 degrees.
This starts the adaption process. During the adaption process, the LMV5 will determine the
thermal response of the system (burner / boiler and attached thermal users). Values for PID
will be calculated based on this information. The LMV5 does this by modulating to minimum
load and letting the system "settle" to a particular pressure or temperature. After this
Go into parameter and
"settling" period, the LMV5 will modulate up to the AdaptionLoad and see how long it takes
then press Enter to start
for the system temperature / pressure to respond.
adaption
Based off of this response, the LMV5 will choose values for P, I, and D. These calculated
values are implemented by choosing "Adaption" under StandardParam .
NOTE: Adaption has to be started when the burner is running and a representative load
exists on the system.
This load is used to determine the thermal response of the system during adaption only.
100%
40-100%
LMV5 will travel to this load during the heating phase of the adaption.
Read Only
Software version of the load controller.
Page 35
HOME
Description
P - LIST
Technical Instructions
LV5-1000
LMV
x x x
x x x
x x x
x x x
x x x
x x x
x x x
x x x
x x x
Section 3