LEGEND - Password Access: (U)=User, (S)=Service, (O)=OEM, Shaded = Commonly Used, ** = Must Set, X = Has Function, / = Partial Function
Menu Path
Parameter
Standardize (O)
Params & Display>
BurnerControl>
StandardFactor (O)
Configuration>
ConfigFlameDet>
FlameSignal
FlameSig QRI_B (U)
FlameSig ION (U)
NOTE: On an LMV52, it is recommended to set the following six flame scanner parameters for "1 Sensor". These parameters are unavailable on an LMV51.
SensExtranlGas (O)
Params & Display>
BurnerControl>
Configuration>
ConfigFlameDet
SensPilotPhGas (O)
SensOperPhGas (O)
SCC Inc.
Default
Range
Sets a datum for a "normal" flame, so that a "normal" flame can be displayed as 100% flame
signal on the OperationalStat screen. If an 82.3% flame is present and the flame
Go into parameter then
standardization is performed, what was displayed as 82.3% is now displayed as 100%. This
press Enter to start
parameter does not affect when a lockout occurs due to low flame signal. This standarization
is performed when a normal flame exists in the burner.
Can be viewed to see what percent raw flame signal will result in 100% flame signal being
XXXX%
0-100%
displayed on the OperationalStat screen. If the flame signal is not standardized, XXXX % will
(Not Set)
appear, indicating actual flame strength is displayed.
This can be viewed to see the raw flame signal (in %) from the flame scanner (IR or UV).
Read Only
Flame failure at 20%. This signal refers to INPUT terminal X10-02.1 or X10-02.2.
This can be viewed to see what raw flame signal (in %) is being sent to the LMV5 by an
Read Only
ionization probe (flame rod) on terminal X10-03.1. The LMV5 will alarm when this value is
less than about 20%.
For the LMV52, this defines how the combustion chamber will be supervised during the
period when the fuel valves are closed (gas firing).
The choices for supervision during this phase are as follows:
1) 1 Sensor: Either a flame rod (ION) or scanner can be connected and used. Both cannot be
connected.
2) QRI_B | ION: Both sensors can be connected. A flame signal on either will cause a signal
See
1 Sensor
to be registered.
Description
3) QRI_B & /ION: Both sensors can be connected. Flame must be detected by QRI_B and not
ION.
4) QRI_B: Both sensors can be connected. Only QRI_B is used.
5) ION &/QRI_B: Both sensors can be connected. Flame must be detected by ION and not
QRI_B.
6) ION: Both sensors can be connected. Only ION is used.
For the LMV52, this defines how the pilot for gas firing is supervised. Options 1 thru 6 as
described in parameter SenExtranlGas also apply to this parameter. Additionally, there is
1 Sensor
See Above
one option added for this parameter. This option is:
7) QRI_B & ION: Both sensors can be connected. Both sensors must detect a flame at the
same time or a flame failure will occur.
For the LMV52, this defines how the main flame for gas firing is supervised. Options 1 thru 7
1 Sensor
See Above
as described in parameters SensExtranlGas and SensPilotPhGas also apply to this
parameter.
Page 15
HOME
Description
P - LIST
Technical Instructions
LV5-1000
LMV
x x x
x x
x x
x x
Section 3