Technical Instructions
LMV Series
Document No. LV5-1000
Load Controller Software Update: Version 0160 to 0180 (continued)
2. Analog output X63 has one additional range added: 0-20 mA.
3. The value of the analog output (e.g. load, temperatures, O2, etc.) can now be selected.
4. The measuring range for temperature input X60 added an additional option for Pt100,
Pt1000, and Ni1000 sensors: 1562 °F [850 °C].
5. A new variable temperature range was added via parameter var. RangePtNi.
6. Parameter MinActuatorStep also becomes active for external load controller modes.
Load Controller Software Update: Version 0180 to 0210
The following updates were made with LMV5 load controller software version 0210:
1. The starting point for ThermalShockProtection was increased from 0% output to minimum
output. At the deactivation of ThermalShockProtection, the load controller is initiated with the
current output. Previously, the LMV5 moved to low fire and then to the current load.
2. At the end of the thermal shock protection program, the current temperature acquired by
the Ni/Pt1000 sensor programmed as an additional sensor is now updated. The change only
applies to a Ni/Pt1000 sensor, not to a Ni/Pt100 sensor. The temperature is displayed by the
AZL52/ Modbus.
3. When using flue gas recirculation (FGR) mode "TCautoDeact", in the event of an error of the
Pt/Ni1000 sensor, a lockout is not triggered.