Figure 5-29 Connecting light output power cables for the PDC
----End
Follow-up Procedure
After connecting cables, use diagonal pliers to cut cable inlet and outlet holes on rodent-proof
meshes based on the number and specifications of cables, install the rodent-proof meshes on
the top of the PDC, and seal the cable inlet and outlet holes with firestop putty.

5.5.5 Connecting Signal Cables for the PDC

Procedure
Step 1 Connect the PDC monitoring cable to the monitoring port on the side of the MDU screen on
the PDC front door.
Issue 07 (2019-04-15)
Connect the light power cables to XT2-1–XT2-6.
When the air conditioner adopts two MCCB inputs, the L wires of the light power cable
should be routed from the right side of the cabinet rear door, while the N/PE wires of
XT2-4–XT2-6 should be connected to the left N/PE bars through the cable beam in the
middle of the PDC.
When Modbus TCP is used, connect one end of the network cable to the FE port in the PDC, and
connect the other end to the collector.