Huawei PDU8000 User Manual page 65

Modular integrated pdc v1.0
Hide thumbs Also See for PDU8000:
Table of Contents

Advertisement

PDU8000 Modular Integrated PDC V1.0
User Manual
Main
Second-Level
Menu
Menu
Issue 07 (2019-04-15)
Third/Fourth-Level
Menu
System
Rated
Param.
frequency (Hz)
Rated line
voltage (V)
Route 1 Rated
Current, Route
2 Rated
Current (A)
Route 3 Rated
Current, Route
4 Rated
Current (A)
Route 1 CT
Ratio, Route 2
CT Ratio
Route 3 CT
Ratio, Route 4
CT Ratio
Br. cur. shock
threshold
x harmonic
frequency
y harmonic
frequency
z harmonic
frequency
Harmonic
alarm
detection
enable
Main input
overfrequency
Main input
underfrequenc
y
Main input
breaker off
Main input
surge
protection
Copyright © Huawei Technologies Co., Ltd.
7 MDU Commissioning Guide
Function
Specifies the rated frequency of
the PDU8000. The value ranges
from 45 to 65.
Specifies the rated voltage of the
PDU8000. The value ranges from
100 to 480.
Specifies the rated current of the
PDU8000. The value ranges from
50 to 800.
Specifies the rated current of the
PDU8000. The value ranges from
50 to 800.
The value ranges from 50 to 800.
The value ranges from 50 to 800.
The value ranges from 150 to
500.
2–63
2–63
2–63
The alarm can be enabled or
disabled.
Preset
Value
50
380
N/A
N/A
N/A
N/A
300
5
7
11
Disable
Enable
Enable
Enable
Enable
58