Huawei PDU8000 User Manual page 68

Modular integrated pdc v1.0
Hide thumbs Also See for PDU8000:
Table of Contents

Advertisement

PDU8000 Modular Integrated PDC V1.0
User Manual
Main
Second-Level
Menu
Menu
Maint.
Issue 07 (2019-04-15)
Third/Fourth-Level
Menu
Upper load
cur. thres. (%)
Lower load
cur. thres. (%)
3-phase load
imb. (%)
Neutral-groun
d overvoltage
(V)
Setting Wizard
Remove USB
Upgrade Software
Load Config.
Download Config.
Download Logs
Export Alarms
Export E-labels
Import MD Config
Extend MD Config
Copyright © Huawei Technologies Co., Ltd.
7 MDU Commissioning Guide
Function
Specifies the upper alarm
threshold relative to the rated
current. The value ranges from
80.0 to 100.0.
Specifies the lower alarm
threshold relative to the rated
current. The value ranges from
30.0 to 80.0.
Specifies the alarm threshold
relative to the balanced
three-phase current. The value
ranges from 0.0 to 50.0.
Specifies the alarm threshold
relative to the neutral-ground
voltage. The value ranges from 3
to 500.
Enables you to set language, time,
network, and system parameters.
Enables you to remove the USB
flash drive from the MDU.
Enables you to upgrade software
by using a USB flash drive.
Enables you to load system
parameters from a USB flash
drive to the system in batches.
Enables you to download
configuration information to a
USB flash drive.
Enables you to download
operation logs to a USB flash
drive.
Enables you to download alarm
information to a USB flash drive.
Enables you to download E-labels
of the PDC to a USB flash drive.
Enables you to upload
configurations using a USB flash
drive.
Enables you to extend
configurations using a USB flash
drive.
Preset
Value
80.0
60.0
15.0
45
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
61