Huawei PDU8000 User Manual page 59

Modular integrated pdc v1.0
Hide thumbs Also See for PDU8000:
Table of Contents

Advertisement

PDU8000 Modular Integrated PDC V1.0
User Manual
Procedure
Step 1 Switch on all SPD circuit breakers.
Step 2 Switch on the upstream input circuit breakers to power on the PDC.
Step 3 After the MDU screen starts, set the language, time, date, network parameters, and system
parameters by using the Setting Wizard.
Table 6-5 Setting wizard
Item
Language
Data and Time
Network Param.
System Param. 1
For system security purposes, change the preset password upon first login.
Step 4 After the quick settings are complete, if the monitoring page displays abnormal alarms, clear
them.
Step 5 Switch on the input switch of the PDC.
Step 6 Switch on the output circuit breakers in the PDC in sequence to power on the corresponding
devices and check whether the monitoring parameters on the display panel are correct.
----End
Issue 07 (2019-04-15)
If the surge protection module indicator is green, the SPD is running properly. If the surge protection
module indicator is red, the surge protection module is faulty and must be replaced immediately.
If the power indicator on the front panel of the PDC lights up, the PDC is powered on properly.
Set Rated frequency and Rated line voltage on the System Param. screen based on the actual
situation and retain default values for other system parameters.
The user name is admin (preset password: 000001).
Copyright © Huawei Technologies Co., Ltd.
Parameter
-
Date format
YYYY-MM-DD
Time zone
Time (H:M:S)
IP address assign
Rated frequency
Rated line voltage
6 Power-On Commissioning
Setting
English
Set as required
Actual date
Actual time zone
Actual time
Automatic (DHCP)
Set as required
Set as required
52