Dip Switch - Huawei PDU8000 User Manual

Modular integrated pdc v1.0
Hide thumbs Also See for PDU8000:
Table of Contents

Advertisement

PDU8000 Modular Integrated PDC V1.0
User Manual

7.3 DIP Switch

A dual in-line package (DIP) switch is located at the rear of the MDU.
Figure 7-14 DIP switch
The following lists the functions of the DIP switch:
Table 7-3 Status combinations of DIP 2, DIP 3, and DIP 4 and their functions
Function
Clear
historical
alarms.
Clear
logs.
Restoring
factory
settings
Issue 07 (2019-04-15)
DIP1: Controls the CAN build-out resistor and is set to ON by default.
DIP2 to DIP4: Work together with specified buttons to clear historical records and logs
and restore factory settings.
To clear historical records and logs, you must log in as the admin user.
Status
Combination
Copyright © Huawei Technologies Co., Ltd.
DIP
DIP
DIP
2
3
4
ON
OFF
OFF
OFF
ON
ON
ON
ON
OFF
7 MDU Commissioning Guide
Button
Action
Operation
Press the
Clear historical
Active Alarm
alarms.
for 10s.
Press the
Clear operation
logs (APP/LUI).
Buzzer Off
for 10s.
The MDU
automatically
restarts during
the process.
Press the
The MDU
automatically
Buzzer Off
for 10s.
restarts after
factory settings
are restored.
68

Advertisement

Table of Contents
loading

Table of Contents