Water-cooled
Hide thumbs Also See for ACS5000:
Table of Contents

Advertisement

2. Check that a pipe joint has been slid on one pipe end of two adjoining
water pipes.
3. Line up the transport units as shown in "Appendix C –
Mechanical drawings".
The units can be lined up either beginning from the left or the right.
4. Align the transport units.
5. Verify the following alignment parameters:
6. Maximum values for the axial misalignment and the angular
deflection of two adjoining water pipes are not exceeded
Axial misalignment: ± 3 mm
Axial deflection: 5°
7. Screw holes are exactly aligned.
3BHS799208 E01 REV E
ACS5000 WATER-COOLED USER MANUAL
05 MECHANICAL INSTALLATION