Drive-Cliq Interfaces X400, X401, X402; Terminal Block X40 External 230 Vac Auxiliary Infeed; Options - Siemens SINAMICS S120 Manual

Cabinet modules liquid cooled
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Cabinet Modules
6.2 Active Line Connection Modules
6.2.2.4

DRIVE-CLiQ interfaces X400, X401, X402

Table 6- 17
Connector
Blanking plate for DRIVE-CLiQ interfaces (50 pcs.) Article number: 6SL3066-4CA00-0AA0
6.2.2.5
Terminal block -X40 external 230 V AC auxiliary infeed
Terminal block -X40 provides you with the option of connecting an external auxiliary infeed
(such as an uninterruptible power supply) that is independent of the main infeed. The
connection may be protected with up to a 16 A fuse.
Table 6- 18
Terminal
1
2
5
6
Max. connectable cross-section: 2.5 mm²
6.2.3

Options

Note
Additional information
The individual options are described in Chapter "Options".
166
DRIVE-CLiQ interfaces X400, X401, X402
PIN
Signal name
1
TXP
2
TXN
3
RXP
4
Reserved, do not use
5
Reserved, do not use
6
RXN
7
Reserved, do not use
8
Reserved, do not use
A
+ (24 V)
B
M (0 V)

Terminal block X40 external 230 VAC auxiliary infeed

Designation
Technical data
L1
Factory-installed jumper to terminal 2; this jumper must be re-
moved if an external infeed is used.
L1
Connection of external 230 VAC auxiliary infeed: L1
N
Factory-installed jumper to terminal 6; this jumper must be re-
moved if an external infeed is used.
N
Connection of external 230 VAC auxiliary infeed: N
Technical data
Transmit data +
Transmit data -
Receive data +
Receive data -
24 V power supply
Electronics ground
Cabinet Modules liquid cooled
Equipment Manual, 04/2020, A5E37067587A