Siemens SINAMICS S120 Manual page 77

Cabinet modules liquid cooled
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Figure 4-2
Table 4- 2
Dimensions of the cable lugs
Screw / bolts
Connection cross-section
M8
M10
M10
M12
M12
M12
M16
Attaching 2 cable lugs per phase
The cable lugs can be attached as shown in the following diagram if, at one connection per
phase, 2 cable lugs can be connected.
Figure 4-3
Cabinet Modules liquid cooled
Equipment Manual, 04/2020, A5E37067587A
Dimensions of the cable lugs
d2
[mm²]
[mm]
70
8.4
185
10.5
240
13
95
13
185
13
240
13
240
17
2 cable lugs per connection
b
l
[mm]
[mm]
24
55
37
82
42
92
28
65
37
82
42
92
42
92
Electrical installation
4.5 Connections
c1
c2
[mm]
[mm]
13
10
15
12
16
13
16
13
16
13
16
13
19
16
75