K82, Terminal Module For Activating Safety Functions "Safe Torque Off" And "Safe Stop - Siemens SINAMICS S120 Manual

Cabinet modules liquid cooled
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

9.18 K82, terminal module for activating safety functions "Safe Torque Off" and "Safe Stop 1"

9.18
K82, terminal module for activating safety functions "Safe Torque
Off" and "Safe Stop 1"
Availability of option
This option is available for the following S120 Cabinet Modules:
● Motor Modules
Description
The option K82 (Terminal Module for activating "Safe Torque Off" and "Safe STOP 1") is
used for isolated activation via a variable control voltage range of the safety functions
already present in the standard, which can also be used without option K82.
Use option K82 to activate the following Safety Integrated functions (terminology according
to EN 61800-5-2):
● Safe Torque Off (STO)
● Safe Stop 1 (SS1, time-controlled)
Note
Standard requirements
The integrated safety functions, starting from the Safety Integrated (SI) input terminals of the
SINAMICS components (Control Unit, Motor Module), satisfy the requirements according to
EN 61800-5-2, EN 60204-1, DIN EN ISO 13849-1 Category 3 (formerly EN 954-1) for
Performance Level (PL) d and EN 61508 SIL2.
In combination with the option K82, the requirements specified in EN 61800-5-2, EN
60204-1, as well as in DIN EN ISO 13849-1 Category 3 (formerly EN 954-1) are satisfied for
Performance Level (PL) d and EN 61508 SIL2.
Note
Safety Integrated Function Manual
Detailed and comprehensive instructions and information for the Safety Integrated functions
can be found in the associated Function Manual. This manual is available as additional
documentation on the customer DVD supplied with the device.
Cabinet Modules liquid cooled
Equipment Manual, 04/2020, A5E37067587A
Options
389