K52, Additional Smc30 Sensor Module - Siemens SINAMICS S120 Manual

Cabinet modules liquid cooled
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Options

9.16 K52, Additional SMC30 Sensor Module

Removing the connector jumper in the Voltage Sensing Module VSM10
At the Voltage Sensing Module (VSM10), the connector jumper in terminal X530 on the
lower side of the component must be removed if you are using the cabinet unit on a non-
grounded line supply (IT system).
Use two screwdrivers or a suitable tool in order to relieve the holding springs in the terminal
and then withdraw the connector jumper.
Note
False tripping caused by not removing the connection clip with a non-grounded line supply
Failure to remove the connector jumper on a non-grounded line supply (IT system) can
cause false tripping in case of sensitive IT network monitoring.
• For an ungrounded line supply system (IT system), remove the plug-in jumper.
9.16
K52, Additional SMC30 Sensor Module
Availability of option
This option is available for the following S120 Cabinet Modules:
● Motor Modules
386
Terminal X530 with connector jumper
Relieve the springs and withdraw the connector
jumper
Cabinet Modules liquid cooled
Equipment Manual, 04/2020, A5E37067587A

Advertisement

Table of Contents
loading

Table of Contents