6.4.2.3
X1 - power supply
-X1: Power supply
Table 6- 35
Terminal
L1
L2
L3
PE
max. connection cross-section: 4 mm²
recommended cross-section: 2.5 mm²
Note
Tripping characteristic of the cable protection circuit breaker
As a result of the pump starting current, the cables to the power supply should be protected
using a circuit breaker with tripping characteristic "C".
6.4.2.4
X6 - external 24 V DC power supply
X6: External 24 V DC power supply
Table 6- 36
Terminal
1
3
PE
max. connection cross-section: 4 mm²
recommended cross-section: 2.5 mm²
Cabinet Modules liquid cooled
Equipment Manual, 04/2020, A5E37067587A
Terminal strip X1
Function
Phase L1
Voltage:
Phase L2
•
Phase L3
•
Current consumption: See Technical data
PE connection
Terminal strip X6
Function
M
Voltage: 24 V DC (20.4 to 28.8 V)
Current consumption: max. 1.0 A
+24 V
PE connection
Technical data
3 AC 380 V -10 % ... 3 AC 415 V +10 %
or
3 AC 500 V -10 % ... 3 AC 690 V +10 %
Technical data
Cabinet Modules
6.4 Heat Exchanger Modules
211